Building Construction Fire Resistance Tester, BFR-125, BFR-225, ISO 834, KS F 2275-1, KS F2268-1, KS F2846, KS B6951
Introduction
FESTEC's Building Construction Fire Resistance Tester measures the performance of construction material against standard fire conditions, and satisfies the general requirements, vertical history section material, vertical non-history section material and the fire-proof door's fire proof testing. This equipment tests about the walls, doors, dampers, connections, through type sealing material, etc. such as the product of test for fire resistance.
Standard
ISO 834 : Fire-resistance tests -Elements of building construction Part 1 - General requirements Part 4 - Specific requirements for load bearing vertical separating elements Part 5 - Specific requirements for load bearing horizontal separating elements Part 6 - Specific requirements for beams Part 7 - Specific requirements for columns Part 9 - Specific requirements for non-load bearing ceiling elements
KS F 2275-1 Methods of fire resistance test for elements of building construction-General requirements
KS F 2268-1 Fire resistance test for door assemblies
Other Standards : BS 476(20-23), BS EN 1363(1-2), BS EN 1364(1), BS EN 1365(1), BS EN 1366(1-3), BS EN 1634-1, ASTM E 119, ASTM E 814, UL 10(B-C), UL 263, UL 1709, UL 1479, UL 2079, ISO 3008, ISO 3009
Features
Vertical/Horizontal/Small Testing Furnace - Testing main body and Refractories ; Inside dimension : 4,000(W) x 3,000(H) x 1,100(D)mm - Pattern & PID Control System - HMI & Control System - Additional facilities ; Testing specimen frame (Land, Ship, Boring Testing 1 ea) ; Hydraulic Unit & Cylinder ; Testing specimen frame stock and work table * Excluding testing furnace frontal work Lifter
Combustion blocking testing device (Option Parts) Casing & Frame Moving & Sealing Unit ; Hydraulic Unit & Cylinder ; LM Guide Rail ; Sealing Gasket - Additional devices and piping ; Air Supply Fan ; Flow rate and attachment device - Operating Panel
Exhaustion gas discharge device (Option Parts) - I.D FAN - Exhaustion Duct - Exhaustion Amount Control Damper ; Strength and Stack material : Carbon Steel ; Excluding gas collection hood at the upper part of front of the testing furnace
Specification
Model
FT-BFR-125, FT-BFR-225, FT-BFR-325
Size
3,890(W) x 1,970(D) x 4,940(H)mm(Vertical) 4,925(W) x 3,700(D) x 4,162(H)mm(Blocking Smoking) 6,230(W) x 1,755(D) x 7,095(H)mm(Dust Collector)
Power
AC 380V 3-phase, 50/60Hz, 500A
Weight
Approx. 7,500kg(Vertical Tester), Approx. 3,500kg(Blocking Smoking), Approx. 5,700kg(Dust Collector)
Manual
Supply
Exhaust
Minimum 800m3/min
Utilities
Gas, Hydraulic systems, Water, Personal Computer
Test Result
After applying a certain amount of head within the fireproof door (ISO Curve) and measure the degree of twist (disposition) and any damages due to heat, and additionally measure any flow of heat towards the exterior.
During test time, it distribute pressure measurement(Pa) and print for graph
During test time, it distribute temperature measurement(oC) and print for graph
During test time, record characteristic of specimen and damage
Building Construction Fire Resistance Test...
Description
Product Inquiry
Purchase Product Catalog
Payment & Shipping Conditions:
- Payment: We accept payment through Paypal Only.
- Shipping: We will ship the catalog once the payment is received. And you will be receiving the catalog with in 10 -14 busines days. Shipping might be delayed in due to international shipping conditions which is depends on the countries receiveing. In case hard copy of catalog is not available then we will ship the soft copy.
- Refund: We can refund the order before shipping process was initiated. Incase Catalog not available, we will make sure to refund the order.
- Note: This is a Catalog Produt.
Share Building Construction Fire Resistance Test... in Social Media