Transformer Diagnostics Monitor
Introduction
Integrated diagnostic monitoring system on 110~330kV transformer insulation condition
Very easy to integrate it into existing protection systems
Monitors bushing insulation based on the sum of currents method
Monitors PD caused by bushing and transformer insulation defects
Monitors load current signals to detect critical winding deformation resulting from short circuits
Estimates an efficiency of the transformer cooling system
Noise elimination method: T-F analysis, polarity discrimination, TOA method
Two years archive of events
TDM software for Expert analysis
Features
1. Main insulation state
Monitors partial discharges in transformer insulation
Identifies defect type by correlation of partial discharges intensity and type of the revealed defect with chromatography data
2. Bushing insulation state
Monitors bushing tan delta, capacitance and conduction currents
Monitors partial discharges in HV bushings
3. Asymmetry of Phase windings impedance
Monitors the transformer neutral current indicating asymmetry in the windings impedance, which occurs when windings deformation as result of short circuit currents
4. Efficiency of Cooling system
Monitors temperature difference between the top and the bottom parts of the transformer tank along with the ambient temperature and load
System Configuration
Specifications
Operation Temp.
-30~70°C
Bushing sensor inputs
3
RFCT sensor input
1
Oil temperature sensor inputs
2, RTF Pt-100
Ambient temperature sensor input
1, RTD Pt-100
Ambient humidity sensor input
1
Load current sensor inputs
3, CT
Neutral current sensor input
1, CT
Communication interfaces
USB/RS-232/RS-485
Communication protocol
Modbus RTU
Output Relays
3(Status, Warning and Alarm)
Heater Relay
1
Power Supply
100~240VAC, 50/60Hz
Total dimension, mm
230x170x40